HOME > Products > G3 MMS

Machinery Monitoring Systems and Condition Monitoring Systems

GENCON offers protection and condition monitoring systems for all your machinery.

2023-11-24

G3 Series Machinery Monitoring System Iss1.0.pdf


• Absolute and Relative Vibrationimage.png

• Displacement and Thrust Position

• Speed, Phase and Reverse Rotation

• Differential and Casing Expansion

• Rod Drop

• Temperature

• Shutdown Protection

• Processed Analogue Output

• Modbus Communication.

• Colour LCD display.

• Turbines, Compressors, Fans, Pumps, Motors, and Centrifuges.


Description


The G3 Machinery Monitoring System (MMS) is a high-performance signal conditioning unit, providing a universal platform for the interfacing of various sensor types in compliance with the API 670 standard. Each of the four channels can be independently programmed to provide continuous monitoring and protection functionalities across a broad range of measurements (including vibration, position, expansion, speed, etc). Utilising the latest DSP technology, once a channel is set up and running, the resulting alarm relay and analogue output are independent from the remaining monitor functionalities, resulting in a scalable high integrity configuration.

The MMS monitor is provided with an intuitive colour LCD display and drive facility to provide immediate viewing and access to the machine parameters. Several modes of display are available including bar graph, FFT and an alarm historian.

The MMS monitor provides the necessary power source for the selected transducer, providing for 2 (ICP type) or 3 – wire accelerometer variants, ± 24V proximity probe systems and a range of speed sensors.

Each transducer signal is buffered and available via the front panel analogue connection arrangement and a USB interface is provided for programming of the unit and storage of channel history and settings.

The MMS monitor is designed for mounting in standard 3U rack assemblies with a dual redundant power supply option. The MMS system offers excellent channel density with up to 24 measurement channels in a 3U format.

Each channel can provide independent analogue outputs of current and voltage for DCS connection in addition to an alarm relay. Further alarm relay expansion is possible through connection to digital outputs at the rear of the monitor.


Datasheets:G3 Series Machinery Monitoring System Iss1.0.pdf